The City of Fayetteville is in frequent communication with our partners at the Cumberland County Department of Public Health and health officials at local, state, and federal agencies who are monitoring the situation and providing guidance on how to respond to COVID-19. Our top priority is to maintain essential services for our community while protecting the health and safety of our residents and employees. MORE INFO

Plumbing Inspections

Permitting & Inspections Department

plumbing

Permit Inspection Work

Work must be inspected during each phase of construction before work is concealed and/or continued by the permit holder or their agent. The inspection request is called into Dispatch at 910-433-1768 or:

433 Hay Street
1st Floor - City Hall
PO Box 1846
Fayetteville, NC 28302-1846

 

Required Plumbing Inspections

Underground Water: Inspected before being covered and before the building inspector's slab inspection, if slab construction.

Underground Waste: Inspected before being covered and before the building inspector's slab inspection, if slab construction.

Rough-in: Before insulation and/or sheetrock has been installed. This addresses the water, venting, building sewer, and drains.

Above the Ceiling: Before ceiling tile is installed. Inspection addresses all plumbing piping above the ceiling.

Sewer: Before covering.

Water Supply: Before covering.

Grease Traps: Before covering.

Grease Sand Interceptor: Before covering.

Final: Job is installed and fixtures are in place.


Common Mistakes Identified During a Plumbing Inspection

  • Not ready
  • Access- doors locked
  • Need D.W.V. test
  • D.W.V. leaking
  • Backwater valve is not installed
  • Test water pipe
  • Nail plates missing
  • Freezing, no insulation
  • Final testing (no water on)
  • Venting is missing or incorrect
  • Thermal expansion is missing
  • Slope or fall of pipe is incorrect
  • Washing machine stand pipe is not within 18 inches minimum and 48 inch maximum
  • Water heater drain pan must be a minimum of 1 inch and cannot use PVC pipe for drain
  • Need cleanout